Frequently asked questions
Frequently asked questions about our aquaPROFI liquid filter series and other filter housings. Engineering, manufacturing and support from one hand.
Applications & Technology
What applications is the aquaPROFI series designed for?expand_more
The self-cleaning filters are used in five areas: process liquids, surface-water intake, cooling water treatment, wastewater conditioning, and closed cooling circuits in data centers. A typical case: water from a river or lake feeds heat exchangers; without filtration they foul and must be disassembled at great effort. An aquaPROFI protects the heat exchangers and significantly reduces maintenance effort. Cleaning takes place during operation, without flow reversal.
Are aquaPROFI filters suitable for drinking water?expand_more
Our liquid filters do not have a general drinking-water approval as a complete system and do not produce drinking water on their own. However, the housings and all wetted components are made of food-safe materials. For stainless-steel housings we offer an optional electropolishing treatment, frequently requested in drinking-water applications. It produces an especially smooth, passivated surface where biofilm and deposits adhere less readily, and improves cleanability. The associated certificate chain, from the coating down to the sliding bearing, is available on request. However, aquaPROFI filters are an important part of the treatment chain as pre-filtration for surface water or well intake.
Which filtration grades are available for the aquaPROFI?expand_more
The screen elements are available from 2–800 µm; the multilayer stainless-steel mesh covers standard grades from 2 to 500 µm. For heat-exchanger protection, 80–100 µm has proven sufficient in practice. We match the optimal grade to your application during the design phase.
What flow rate does the aquaPROFI series achieve?expand_more
Depending on the model, the series covers flow rates from 50 to 250 m³/h, depending on filtration grade and dirt load. The AP 3025 reaches up to 100 m³/h, the AP 5025 up to 150 m³/h (each at 100 µm). For higher flow rates we operate multiple filters in parallel (see "Are the filters scalable and redundantly extendable?"). This way we have already realized flow rates of more than 1,000 m³/h.
Does self-cleaning require a reversal of the flow direction?expand_more
No. Cleaning takes place fully during ongoing operation, reversing the flow direction as with classic backwashing filters is never required. Your process is supplied with filtrate at all times.
How does self-cleaning during operation work?expand_more
A flush valve opens into a non-pressurized line. Due to the resulting pressure differential relative to the line pressure, water not only continues to flow through the screen, but also into the suction nozzles, which travel across the screen mesh. A special geometry creates a vacuum lens in front of the screen that removes the dirt from every spot in a targeted manner. This suction instead of classic backwashing brings many advantages, not least for fibrous dirt loads that would otherwise entangle in the screen mesh. Cleaning is triggered automatically as soon as the differential pressure exceeds a predefined threshold; timed or manual cleaning is also possible. One flush cycle takes about 30 seconds; the flush water volume is roughly 60–120 liters depending on model and intake pressure, and is discharged into a drain line.
What operating pressure is required?expand_more
An operating pressure of 1.5–2.5 bar is required, depending on application and pressure-holding system. This pressure is essentially needed during the approx. 30-second flush phase: if the system pressure is not permanently sufficient, it can be raised only for the flush phase, e.g. by temporarily adding a pump.
Which pressures and temperatures are permissible?expand_more
The maximum permissible pressure is 16 bar (PN10/PN16; other pressure ratings on request). The permissible media temperature is −15 to +110 °C; for powder- or Rilsan-coated housings, lower limits apply depending on the medium (55 °C and 85 °C respectively). We have also manufactured filters for temperatures up to 160 °C. Thanks to our high vertical integration in-house it is worth contacting us for special applications.
What is needed for installation and operation?expand_more
The filter fits into existing piping systems; no foundation is required. Operation needs four things: a power supply (230 V/400 V), pressure-bearing lines (1.5–2.5 bar depending on application), prepared pipe connections, and a drain line for the flush water (hose or HT pipe). Operation is possible vertically or horizontally; the vertical orientation is preferred. Special requirements such as two or more filtrate outlets are implemented individually.
How is the filter controlled and monitored?expand_more
By default a Siemens SIMATIC S7-1200 with KTP-700 touch panel controls the filter (alternative: LOGO!). Cleaning is triggered automatically via differential-pressure monitoring; timed or manual cleaning is possible. Operating and fault messages appear on the panel and are additionally available via potential-free contacts for plant monitoring. Optionally we supply Ethernet or ProfiBus interfaces, a UPS for orderly shutdown during power outages, and explosion protection per II 2G Ex db IIC T5 Gb.
Are the filters scalable and redundantly extendable?expand_more
Yes. Multiple filters, both aquaPROFI housings and other filter housings, can be operated in parallel under a common control system, increasing filter area and throughput as needed. In redundantly designed systems (e.g. dual basket filters for data centers), filtration continues without interruption during maintenance or failure of one filter.
Selection & Engineering
Who should submit an inquiry?expand_more
Everyone who plans or is responsible for filtration: planners, technical decision-makers and water masters. Many planning offices contact us early in the project phase and then include our filters in their scope-of-works documents. Starting point is the contact form on filterprofi.de — non-binding and free of charge: https://filterprofi.de/en/#contact
I do not know flow rate, pressure or filtration grade — can I still inquire?expand_more
Yes. In early planning these values are often not fixed yet, for instance when the pump has not been sized. Simply tell us your application: for heat-exchanger protection, 80–100 µm has proven sufficient in practice. We clarify the operating pressure at system level; 1.5–2.5 bar is required depending on application and pressure-holding system. If that pressure cannot be provided permanently, it is enough to provide it for the approx. 30-second flush phase (e.g. by temporarily adding a pump).
What details should an inquiry contain?expand_more
Operating pressure, desired filtration grade and the housing material. The material can often be derived from the existing pipework: for PE piping, for example, we recommend a steel housing with Rilsan coating. Options include stainless-steel housings (1.4301 or 1.4571, pickled and electropolished) as well as steel housings with anti-corrosion protection by primer, Rilsan or Halar. Any open points are clarified jointly before the quote is prepared.
We want to filter finer than before — what should we consider?expand_more
A finer filtration grade usually reflects a drive to improve or change the process. Important: finer filter media require a larger filter area to maintain flow rate and service life. We match both to your application during design.
Inquiry, Quote & Planning
What happens after I submit an inquiry?expand_more
Your details are evaluated internally and turned into a quote. We are an engineering office with attached manufacturing; around 95 % of the value creation happens in-house. If key figures are missing for a solid design, we get in touch and clarify them in a direct conversation.
Are consultancy and quotations subject to a charge?expand_more
No. Our quotations are always non-binding and free of charge. Clarifying missing key figures and design consultancy are part of the quoting process; you decide on realization afterwards.
Can we include your filters in our CAD planning?expand_more
Yes. On request we provide 3D models in STEP format. This lets you incorporate our filters into your CAD planning before purchase and account for space requirements and connections from the start.
Operation, Maintenance & Alternatives
We currently run a sand filter — what changes with aquaPROFI?expand_more
Sand filter systems are large and maintenance-intensive: maintenance work can take three to ten days, time in which no filtrate is available (empirical values from our projects). The compact aquaPROFI housings are opened and serviced by a single person; after one to three hours the filter is back in service.
Does Filter Profitlich Maschinenbau also offer maintenance?expand_more
Yes. If you lack the necessary maintenance personnel, have your liquid filters serviced by us. You decide whether maintenance is called on demand or covered by a maintenance contract.
Model overview
| Property | AP 725 download | AP 3025 download | AP 5025 download | AP 7025 download |
|---|---|---|---|---|
| Filter area | 1,000 cm² | 3,000 cm² | 5,000 cm² | 7,000 cm² |
| Filtration grade (screen) | 2–800 µm | 2–800 µm | 2–800 µm | 2–800 µm |
| Max. flow rate | up to 50 m³/h | up to 100 m³/h (at 100 µm) | up to 150 m³/h (at 100 µm) | up to 250 m³/h |
| Connections in/out | DN25–DN80 | DN80–DN100 | DN125–DN150 | DN150–DN250 |
| Filter volume | approx. 15 l | approx. 50 l | approx. 70 l | approx. 120 l |
| Weight | approx. 45 kg | approx. 95 kg | approx. 110 kg | approx. 130 kg |
| Max. operating pressure | 16 bar (PN10/PN16) | 16 bar (PN10/PN16) | 16 bar (PN10/PN16) | 16 bar (PN10/PN16) |
| Permissible temperature | −15 to +110 °C | −15 to +110 °C | −15 to +110 °C | −15 to +110 °C |
All models: housings in stainless steel (1.4301 or 1.4571, pickled and electropolished) or steel (S235JR) with primer, Rilsan or Halar coating; seals EPDM or FKM; food-contact plastic parts in POM; screen mesh made of multilayer stainless-steel composite 1.4401/1.4404.
Contact
Filter Profitlich Maschinenbau GmbH · Am Honnefer Kreuz 59 · 53604 Bad Honnef, Germany